ChlorGuard Control Panel - Technical Specifications

chlorine gas emergency shut off

Dimensions ( H x W x D) 760mm x 415mm x 315mm
Construction Zintec steel welded construction. Separate pneumatic & elactrical compartment. Hinged lockable outer cover c/w 3 mm perspex panel
Protection IP 55
Finish TBC
Power Supply 110V OR 230V
Control ~ Pneumatic Manual, Automatic, Isolate via status control levers door mounted
Control ~ Electrical Signal from gas detectors. Manual from remote closure button. Key test switch
Visual Signal Alarm, mains power, stand by low battery, DC fuse, Pressure.
Sinal Telemetry
(Volt free contact)
All N/C or open contacts
Mains power failure, low pressure, Alarm & Levers not in open position.
Solenoid Valves 12V DC
Option 12V DC Power take off for strobe light to indicate:
a) Lever not in auto
b) Reset button not pressed to cancel alarm
Battery 12 V or 2.8 amp hours

EC Conformity

Conforms with:

  • Machinery Directive 98/37/EC
  • Low Voltage Directive 73/23/EEC
  • EMC Directive 89/336/EEC